Koel-All Products 320 KVA - 750 KVA Image Carousal

Diesel

320 KVA - 750 KVA

Koel - Enquiry Brochure

Koel-All Products 320 KVA - 750 KVA Toggle Accordion


Prime Rating at rated rpm (as per ISO8528)  kVA 320 400 500 625 750
kW 256 320 400 500 600
Genset Model   KG4-320WS1 KG4-400WS11 KG4-500WS KG4-625WS KG4-750WS
Frequency Hz 50
Power Factor lagging 0.8
Voltage V 415 (3Ø)
Governing class (As per ISO 8528 Part-V)   G3
DG set Noise level at 1 meter dBA < 75 (Genset with canopy)
Fuel tank capacity (Standard DG set) Ltrs 600 850 850 990 990
✪Weight of genset with canopy approx..)^ Dry Kg 4090 6950 7200 8300 9700
Wet Kg 4200 7150 7400 8450 9950
Overall dimensions of genset^ Length mm 4750 5575 5575 6500 6800
Width mm 1700 2125 2125 2125 2300
Height mm 2005 2610 2610 2710 2715
Electrical Battery Starting Voltage Volts-DC 24
ENGINE
Engine Model   6SL90ETA 4G3 DV8ETA 4G2 DV8ETA 4G3 DV10ETA 4G2 DV12ETA 4G2
Rated output(Prime Continuous rating as per ISO 8528-1) kW 279.5 360 447.2 561.1 662
HP 380 490 608 763 900.6
No. of cylinder Number 6 8 8 10 12
Cubic capacity2 Ltrs 8.86 15.92 15.92 19.9 23.88
Bore x Stroke mm 118 x 135 130 x 150 130 x 150 130 x 150 130 x 150
Rated Speed RPM 1500 1500 1500 1500 1500
Aspiration NA/TC/TA TA TA TA TA TA
Lube Oil change period hrs. 500
Lube oil Sump Capacity Ltrs 27 40 40 50 73
Coolant Capacity Ltrs 36 63 63 80 175
Adblue/ DEF capacity Ltrs 45 45 x 2
ALTERNATOR
Insulation Class   H
Alternator Efficiency (at 100% load) 0.8 pf** % 95.3 93.4 94.8 95.7 94.7
Max Voltage Dip at Full Load 0.8 pf lag   < 20%
Max Time to build up rated voltage at Rated RPM   < 2 sec, provided engine reach the rated speed

Product Features


 ^ Tolerances Apply
✪ These Weight are for handling & transportation only  
**Efficiency of Alternator as per standards IEC60034-1

Notes
AdBlue used should follow ISO 22241. Above specifications are subject to change without prior notice due to continuous technical development
For intermediate ratings, kindly contact nearest Kirloskar office For Site Conditions other than standard operating conditions consult   Kirloskar Oil Engines for available prime power.

ComKirloskarCustomFormsWeb