320 KVA - 750 KVA - Kirloskar Oil Engines Ltd
Diesel
320 KVA - 750 KVA
Prime Rating at rated rpm (as per ISO8528) | kVA | 320 | 400 | 500 | 625 | 750 | ||
kW | 256 | 320 | 400 | 500 | 600 | |||
Genset Model | KG4-320WS1 | KG4-400WS11 | KG4-500WS | KG4-625WS | KG4-750WS | |||
Frequency | Hz | 50 | ||||||
Power Factor | lagging | 0.8 | ||||||
Voltage | V | 415 (3Ø) | ||||||
Governing class (As per ISO 8528 Part-V) | G3 | |||||||
DG set Noise level at 1 meter | dBA | < 75 (Genset with canopy) | ||||||
Fuel tank capacity (Standard DG set) | Ltrs | 600 | 850 | 850 | 990 | 990 | ||
✪Weight of genset with canopy approx..)^ | Dry | Kg | 4090 | 6950 | 7200 | 8300 | 9700 | |
Wet | Kg | 4200 | 7150 | 7400 | 8450 | 9950 | ||
Overall dimensions of genset^ | Length | mm | 4750 | 5575 | 5575 | 6500 | 6800 | |
Width | mm | 1700 | 2125 | 2125 | 2125 | 2300 | ||
Height | mm | 2005 | 2610 | 2610 | 2710 | 2715 | ||
Electrical Battery Starting Voltage | Volts-DC | 24 | ||||||
ENGINE | ||||||||
Engine Model | 6SL90ETA 4G3 | DV8ETA 4G2 | DV8ETA 4G3 | DV10ETA 4G2 | DV12ETA 4G2 | |||
Rated output(Prime Continuous rating as per ISO 8528-1) | kW | 279.5 | 360 | 447.2 | 561.1 | 662 | ||
HP | 380 | 490 | 608 | 763 | 900.6 | |||
No. of cylinder | Number | 6 | 8 | 8 | 10 | 12 | ||
Cubic capacity2 | Ltrs | 8.86 | 15.92 | 15.92 | 19.9 | 23.88 | ||
Bore x Stroke | mm | 118 x 135 | 130 x 150 | 130 x 150 | 130 x 150 | 130 x 150 | ||
Rated Speed | RPM | 1500 | 1500 | 1500 | 1500 | 1500 | ||
Aspiration | NA/TC/TA | TA | TA | TA | TA | TA | ||
Lube Oil change period | hrs. | 500 | ||||||
Lube oil Sump Capacity | Ltrs | 27 | 40 | 40 | 50 | 73 | ||
Coolant Capacity | Ltrs | 36 | 63 | 63 | 80 | 175 | ||
Adblue/ DEF capacity | Ltrs | 45 | 45 x 2 | |||||
ALTERNATOR | ||||||||
Insulation Class | H | |||||||
Alternator Efficiency (at 100% load) 0.8 pf** | % | 95.3 | 93.4 | 94.8 | 95.7 | 94.7 | ||
Max Voltage Dip at Full Load 0.8 pf lag | < 20% | |||||||
Max Time to build up rated voltage at Rated RPM | < 2 sec, provided engine reach the rated speed |
Product Features
^ Tolerances Apply
✪ These Weight are for handling & transportation only
**Efficiency of Alternator as per standards IEC60034-1
Notes
AdBlue used should follow ISO 22241. Above specifications are subject to change without prior notice due to continuous technical development
For intermediate ratings, kindly contact nearest Kirloskar office For Site Conditions other than standard operating conditions consult Kirloskar Oil Engines for available prime power.