Prime Rating at rated rpm (as per ISO8528) kVA 200 250
kW 160 200
Genset Model   KG4-200WS1 KG4-250WS1
Frequency Hz 50
Power Factor lagging 0.8
Voltage V 415 (3Ø)
Governing class (As per ISO 8528 Part-V)   G3
DG set Noise level at 1 meter dBA <75 (Genset with canopy)
Fuel tank capacity (Standard DG set) Ltrs 400 600
✪Weight of genset with canopy (approx..)^ Dry Kg 3080 3990
Wet Kg 3150 4100
Overall dimensions of genset ^ Length mm 4200 4750
Width mm 1450 1700
Height mm 1900 2005
Electrical Battery Starting Voltage Volts-DC 12 24
ENGINE
Engine Model   6K1080ETA 4G2 6SL90ETA 4G2
Rated output (Prime Continuous rating as per ISO 8528-1) kW 183.8 228
HP 250 310
No. of cylinder Number 6 6
Cubic capacity2 Ltrs 6.48 8.86
Bore x Stroke mm 105 x 125 118 x 135
Rated Speed RPM 1500
Aspiration NA/TC/TA TA
Lube Oil change period hrs. 500
Lube oil Sump Capacity Ltrs 25 27
Coolant Capacity Ltrs 28 36
Adblue/ DEF capacity Ltrs 45
ALTERNATOR
Insulation Class   H
Alternator Efficiency (at 100% load) 0.8 pf** % 94.2 94.3
Max Voltage Dip at Full Load 0.8 pf lag   < 20 %
Max Time to build up rated voltage at Rated RPM   < 2 sec, provided engine reach the rated speed

PRODUCT FEATURES


 
^ Tolerances Apply
✪ These Weight are for handling & transportation only
 **Efficiency of Alternator as per standards IEC60034-1

Notes
AdBlue used should follow ISO 22241.
Above specifications are subject to change without prior notice due to continuous technical development
For intermediate ratings, kindly contact nearest Kirloskar office
For Site Conditions other than standard operating conditions consult   Kirloskar Oil Engines for available prime power.
 

ComKirloskarCustomFormsWeb

Enquire Now